TABLE FOR SIZING SEMI-RIGID
COPPER TUBING FROM
HOUSE LINE REGULATOR TO APPLIANCE
NOMINAL
K&L
1/4
3/8
1/2
5/8
3/4
1
O.D
ACR
3/8
1/2
5/8
3/4
7/8
1 1/8
OUTSIDE
0.375
0.5
0.625
0.75
0.875
1.125
INSIDE
0.305
0.402
0.527
0.652
0.745
0.995
LENGTH (FT)
CAPACITY IN
CFH
10
39
80
162
283
402
859
20
27
55
111
195
276
590
30
21
44
89
156
222
474
40
18
38
77
134
190
406
50
16
33
68
119
168
359
60
15
30
61
107
152
326
70
13
28
57
99
140
300
80
13
26
53
92
131
279
90
12
24
49
86
122
262
100
11
23
47
82
116
247
125
N/A
20
41
72
103
219
150
N/A
18
37
65
93
198
175
N/A
17
34
60
85
183
200
N/A
16
32
56
79
170
250
N/A
14
28
50
70
151
300
N/A
13
26
45
64
136
350
N/A
12
24
41
59
125
400
N/A
11
22
39
55
117
450
N/A
10
21
36
51
110
500
N/A
N/A
20
34
48
103
CFH AT 1" PRESSURE DROP
.60 SPECIFIC GRAVITY
LESS THAN 2 PSI INLET PRESSURE
TABLE BASED ON TYPE K COPPER TUBING INSIDE DIAMETER (SMALLEST INSIDE
DIAMETER OF CU PRODUCTS)